A construction worker in a safety vest and hard hat stands holding open a white emergency exit stairwell fire door labeled "Stair C Floor 3,in a commercial building hallway.

How to Maintain Your Buildings Fire Separations ?

Let’s Discuss Closures and Fire Separations

Fire Separations

  • In condos/apartment buildings, suites are fire separated from adjacent rooms, other suites and corridors by fire separations with a minimum fire-resistance rating of 45 minutes.
  • Public corridors are fire separated from the remainder of the building by a fire separation with a fire-resistance rating of not less than 45 minutes.
  • Service rooms are fire separated from the rest of the building by a fire separation with a fire-resistance rating varying from 45 min. to 2 hrs.
  • Exit stairways are fire separated by fire separations with fire resistance ratings that vary from 45 min. to 2 hrs.
  • Elevator shafts have similar fire resistance ratings as exit stairways.
  • Garbage chutes have similar fire resistance ratings as exit stairways.

Closures (Fire Doors & Fire Dampers)

Ontario Fire Code Maintenance Requirements

Damaged Fire Separations Between Different Occupancies

Damaged Fire Separations Between Rooms & Spaces

Damaged Closures (Fire Doors, Fire Dampers)

Maintenance of Closures (Fire Doors, Fire Dampers)

Fire Door Not Self Closing or Latching
Cut Out Grill in Fire Door
Broken Self Closing Device on Fire Door

Operation of Closures

Door in a fire separation

On Going Inspection Maintenance in Your Building

  • Labels are clearly visible and legible.
  • No open holes or breaks are present in the surfaces of the door or frame.
    List item
  • No damage that could compromise the integrity of the fire-protection rating.
  • The door, frame, hinges, hardware, and noncombustible threshold are secure, aligned, and in working order with no visible signs of damage.
  • All parts are intact—nothing is missing or broken.
  • Door clearance does not exceed more than ¾” on the bottom and clearance between the top of the door and the vertical edge should not exceed 1/8” or 1/16”, depending on the type of door.
  • The self-closing device works properly, ensuring the door closes completely when operated from a fully open position.
  • Missing self-closing devices to be re-installed.
  • Hold-open devices and automatic releasing devices should be repaired or replaced if inoperative.
  • Latching hardware should function correctly and secure the door when closed.
  • No auxiliary hardware should interfere with or hinder the operation of the door or frame.
  • No field modifications should have been made to the door assembly that would void the label.
  • Meeting edge protection, gasketing, and edge seals, where required, should be intact and in good condition.
  • Guides, bearings, and stay rolls should be clean and lubricated.
  • Closures in fire separations must not be obstructed, blocked, wedged open, or altered in any way that could prevent their intended operation.
  • Fusible links and heat or smoke-actuated devices should be free of damage, paint, and dirt.
  • Signage on Condo doors for exit stairways to include the stairway ID and floor level.
  • Fire damper fusible links to be clean with no rust, dirt, etc.
  • Fire dampers check they have not activated and obstructing the duct ventilation
  • Fire damper check there are no obstructions such as gables running thru the duct and will not allow to seal the duct opening.
Fire Damper Access Panel
Painted Fire Damper and Fusible Link
Identification of Exit Stairway & Floor Level

No responses yet

    Leave a Reply

    Your email address will not be published. Required fields are marked *